EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system
In-field programmability by DIP Switch
High Density, two channels per unit
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
The single channel Switch/Proximity Detector Repeater D5036S module is a unit suitable for applications requiring SIL 2 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries. The unit can be configured for switch or proximity detector (EN60947-5-6, NAMUR), NO or NC and for NE or ND SPST (D5036D) or SPDT (D5036S) relay output contact.
Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area.